‘Configuration Mode’ :
- To ‘Set’ all Functions & Values, using Front Panel Keypad Switches [guided by ‘Configuration Table’ provided]
- When in ‘Configuration Mode’ all normal operations of Unit are suspended.
- User should ‘exit’ out of ‘Configuration Mode’, without fail.
- ‘Settable’ Functions include : Wide array of Timers, Aux. Outputs, Contact-types of LLOP & Engine Temp. [HWT], Number of Cranking Attempts, Remote Start, Battery Voltage [12/24 VDC], etc..
Other Salient Features include :
‘Emergency STOP’ facility with exclusive Keypad Switch, ‘Remote’ START & STOP facility [with options],
Wide array of Timers, Select No of Crank Attempts, Select Mute time for Audible-Hooter, Isolated Inputs, etc..
Salient Features
- Rugged ‘Flush-mounted’ Unit with Micro Controller technology.
- Wide range of Auxiliary Supply : Unit operates between 06 VDC to 35 VDC ~ continuously variable
- Withstands ‘Cranking-Dropout’ dip upto 0 VDC of Auxiliary Supply upto 01 second [maximum]
- Continuous supervision of Mains [EB] & DG Breaker status, thus ensuring human & equipment safety.
- Internal interlock for Mains & DG Breaker, with LED Indication of respective CB status, for fail safe operation.
- Facility to ‘Select’ : 12V or 24V Battery, with indication & supervision of ‘Selected’ Battery Voltage status.
- TWO spare Terminals for connecting External [Aux. Input] Faults.
- LED Fault Annunciation for : Start fail, LLOP, High Engine Temp., Engine Fault, Low Battery, Aux. Faults 1 & 2.
- Front Panel Keypad Switches provided for : ‘Auto’, ‘Manual’, ‘Accept’, ‘Manual ON/OFF’ & ‘Emergency STOP’.
- Unit has TWO major Modes of Operation ~ viz. : ‘Configuration Mode’ and ‘Run Mode’
- List of Configurable Aux.
- Timers
- Specifications
List of Configurable Aux. Inputs, Outputs & other Options :
- Aux. Input 1
- Aux. Input 2
- Aux. Output 1
- Aux. Output 2
- Aux. Output 3
- Hooter [Mute set]
- LLOP Contact
- Stop Crank on LLOP
- HWT Contact
- Nominal DC Voltage
- Remote Start
- Crank Attempts
- Remote Start on Load
List of Configurable Timers :
- Pre-heat Timer
- Start Delay
- Cranking ON
- Cranking OFF
- Warm-up Time
- Changeover Delay
- Stop Delay
- Cooling Time (Idle Delay)
- Energise to Stop
Technical Specifications |
| DC Supply [working of Unit] |
06 VDC to 35 VDC ~ continuously variable [step less] |
| Choice of Battery Voltages |
‘Select’ : 12V or 24V Battery, with indication & supervision of Battery Voltage status. |
| Battery Under-Voltage Levels> |
Under-Voltage Levels, for supervision with indication : <8 VDC for 12V Battery .&. <16 VDC for 24V Battery |
‘Cranking-Dropout’
dip of Aux. Supply |
Withstands upto 0 VDC ‘Dip’ of Auxiliary Supply [during Cranking] upto 01 second [maximum].
Hence internal batteries / ‘voltage-boosters’ not required. |
| Maximum Operating Current |
40mA [max] at 12V Battery …and… 25mA [max] at 24V Battery. |
| Typical Operating Current |
15mA at 12V Battery …and… 10mA at 24V Battery, at ‘No-Fault’ condition. |
| Mains [EB] & Alternator Inputs |
These TWO Inputs to Unit shall be from: ‘NO’ [Normally-Open], Potential-free Relay Contacts ONLY. |
| Aux. Alarm & Other Inputs |
Aux. Inputs to Unit shall ONLY be from Potential-free dry Contacts of Relays, Micro switches, etc.. |
| Aux. & Other Functional Outputs |
‘SSO’ = Solid-State Outputs, for connecting Coils of External ‘Automotive’/Plug-in’ Relays, with Maximum Coil Watt = 10W. ‘SSO’ switches to Battery-Negative when active. |
| Ambience |
Operate Temp = 0°C to 70°C |
Storage Temp = -10°C to 90°C |
Humidity = Upto 95% RH |
| Enclosure & Terminals |
Industrial Heat-Resistant Plastic Enclosure, with Screw-type Terminals at rear-side for External Connections. |
| Dimensions |
Cutout : 150mm [Horiz] x 110mm [Verti] |
Bezel : 165mm [Horiz] x 125mm [Verti] |
Depth : 75mm |
Note : Product improvement is a continuous feature. Specifications / Design listed in this publication are therefore subject to revision, without notice.
|